30 18.01. 6755441_03
ANL-ANLH 020-202
EN
SEASON CHANGE controlled from the PR3
ON/OFF CONTROL from the PR3
Confirm the selection pressing key and exit the
menu with the key
Once the PR3 remote panel is enabled the change of
season selection can be made directly from the switch
. The unit will automatically switch on and off
with the selected operating mode.
For further information refer to the USER manual.

9. OPERATING CHARACTERISTICS
9.1. COOLING SETPOINT

9.2. HEATING SETPOINT

Intheeventofamomentarypowerinterruponthe
selectedoperangmodewillberetainedinmemory.
9.3. COMPRESSOR DELAY TIMERS
Toavoidexcessivecompressorstartstwofunconsare
provided:
- Minimum time from last stop 60 seconds in cooling
mode.
- Minimum time from last start 300 seconds in heat-
ing mode.
9.4. CIRCULATING PUMPS
Thewiringschemacprovidesoutputstocontrol
thecirculangpumps.Thesystemsidepumpstarts
immediatelyandaer30secondsofoperaon,when
thewaterowisstabilised,thepressuredierenal/
owswitchcontrolfunconisenabled.Ifnoalarms
are present the unit will start.
9.5. 
The alarm
11
isalwaysacveeveninstandbymode.
To prevent damage to the plate heat exchanger by
freezingofthewaterwithintheunitisstoppedand
an alarm raised if the water temperature drops below
theminimuman-freezesetpointof3°C.Theunitcan
onlyre-startaeramanualresetandifthean-freeze
sensor reads a water temperature above 4°C
12
. With
theunitinomodeandwithawatertemperature
below4°Cthefactorystandardedelectricheaters
ontheheatexchangerareturnedon,andturnedo
when the water temperature exceeds 5°C. The water
pumpalwaysremainsacve.
9.6. WATER FLOW ALARM
Theunithasalowwaterowratealarmusingafac-
toryeddierenalpressureswitchorowswitch.
Thissafetyacvatesaertherst30secondsofpump
operaonifthewaterowrateisnotsucient.The
operaonofthisalarmstopsthecompressorsandthe
pump.
WARNING
11
Theanti-freezesetpoint
can only be adjusted by an
authorised service centre and
only after verifying that the
hydraulic circuit has the cor-
rect%ofanti-freezesolution.
12
If this alarm occurs immediate-
ly call the authorised technical
service assistance.
WARNING
FOR 230V/1/50Hz UNITS:
The unit is provided with a compres-
sor soft starter. This device contains
capacitors that could overheat
through repeated quick starts. If
power supply is removed wait at
least 3 minutes before powering up.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC ANL080Q and is the answer not in the manual?

AERMEC ANL080Q Specifications

General IconGeneral
BrandAERMEC
ModelANL080Q
CategoryHeat Pump
LanguageEnglish

Related product manuals