EasyManuals Logo
Home>AERMEC>Heat Pump>ANL080Q

AERMEC ANL080Q User Manual

AERMEC ANL080Q
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
32 18.01. 6755441_03
ANL-ANLH 020-202
EN
13. PROCEDURE FOR SELECTION OF SYSTEM TYPE
Several parameters of the MODU CONTROL board
have to be set, based on the type of system the unit is
installed.
These changes of parameters are summarised in the
table below to permit the installer to make the appro-
priate selections of the unit's electronic circuit board.
13.1. HOW TO MODIFY A USER MENU
PARAMETER
To access the USER setting press the key and
confirm the password 000 pressing the key . The
display will show the parameters of the USER index
as three identifying characters; the index remains dis-
played for a second and then is replaced by the value
of the parameter it relates to.
To move to the following parameter use the arrow keys
. To modify a parameter press the key , modify the
value using the arrow keys and confirm the modifica-
tion pressing the key . To exit the menu press the
key .
13.2. HOW TO MODIFY AN INSTALLER MENU
PARAMETER
To enter and modify the INSTALLER menu follow the
same procedure as the USER menu above.

 ANSWER WHAT TO DO


The unit is a cooling only model Go to question 2
Radiant panels Enter in parameter StC (index 3 menu USER) with the value of 35 °C
Fan coil units or low temperature
radiators
Enter in parameter StC (index 3 menu USER) with the value of 45 °C (default value)
Other applications Enter in parameter StC (index 3 menu USER) with the value of 55 °C


Not installed Go to question 3
Installed Enter in parameter PAN (index 9 menu INSTALLER) with the appropriate value:

Season selection controlled from the unit circuit board
ON/OFF control from the PR3

Season selection controlled from the PR3
ON/OFF control from the unit circuit board

Season selection controlled from the PR3
ON/OFF control from the PR3


Not present Go to question 5
Present Enter in parameter ASA (menu INSTALLER) with the value (1)



Not present Go to question 5
Present Enter in parameter AAS (index C menu INSTALLER) with the appropriate value (in seconds):
this parameter shows the reversing time for the three way diverting valve in the circuit for the
production of domestic hot water


Not present No function
Present This parameter enables a digital contact ID (shown on the electrical schematic with the
reference TRA) onto which to connect an ambient thermostat with which to disable the
compressors and electric heaters. Enter in parameter , with the
appropriate value selecting from:
1. 
2. 
3. 
stops compressors and heaters if the parameter value is set to 1
stops compressors, pump and heaters if the parameter value is set to 2
pump alarm (as in the previous software version), if the parameter value is set to 3
WARNING
For more information refer to the USER manual provided with the unit and available on the website
