6
WARNING:
For more information about the features of this accessory or details of its compatibility with MVA systems, refer to the specific documenta-
tion describing the accessory itself.
4. ACCESSORIES
MODBUSGW: This accessory allows
you to manage up to 16 MVA sys-
tems (with a maximum total of 128
indoor units), making a serial Mod-
bus available for supervision with an
external BMS.
BACNETGW: This accessory allows
you to manage up to 16 MVA sys-
tems (with a maximum total of 255
indoor units), making a serial Bacnet
available for supervision with an ex-
ternal BMS.
USBDC: This kit includes a CANBUS to
ModBUS converter and the VRF De-
bugger software; created to meet
the needs of after sales service or
authorised technicians who must
carry out control and debugging
procedures on the MVA range.
WRC: wired Soft-Touch panel this Ac-
cessory is supplied as standard with
all Indoor Units; it is also possible to
purchase an additional WRC Wired
Panel to control a single Indoor Unit
or set of Indoor Units (up to a maxi-
mum of 16), with the same settings
from two separate locations.
WRC1: Simplified control wired pan-
el for Indoor Unit with built-in External
Contact. This panel is particularly
suitable for hotel applications. It can
control a single Indoor Unit or a set
of Indoor Units (up to a maximum of
16) with the same settings from two
separate locations.
CC2: Centralised Control (7" touch
screen display), which can be used
to manage up to 255 Indoor Units
distributed across a maximum of 16
Systems. (Not compatible with mod-
els MVAS22401T - MVAS2802T - MV-
AS3351T).
MVASZC: Simplified Centralised
Control (4,3" touch screen display),
which can be used to manage up
to 32 Indoor Units distributed across
a maximum of 16 Systems.