2.Safety & Symbols
2.1 Safety Precautions
1. All work on the inverter must be carried out by qualified electricians.
2. The device may only be operated with PV panels.
3. The PV panels and inverter must be connected to the ground.
4. Do not touch the inverter cover until 5 minutes after disconnecting both DC
and AC power supply.
5. Do not touch the inverter enclosure when operating, keep away from materials
Safety & Symbols
02
BNT003KTL
BNT004KTL
BNT005KTL
BNT006KTL
BNT008KTL
5.3
7
8.5
10.5
13.5
16
16
16
16
25
Type Max AC Current [A] Rate current of AC breaker[A]
BNT010KTL
BNT012KTL
BNT013KTL
BNT015KTL
BNT017KTL
BNT020KTL
17
21.5
22
27
30
32
25
32
32
32
40
40
Circuit Breaker and Surge Protector Recommendation:
SPD: Lightning protection system, refer to the following options:
AC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 2.5KV
DC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 3.2KV
The wiring distance between the inverter and the distribution box should be at
least 5 meters.
Note:
The Inverter can be only connected to low-voltage grid.
(380/400V/415Vac, 50/60Hz).