Mean Condensing Ambient
Temperature °C 25°C 30°C 35°C 40°C 45°C 48°C
Output kW Output kW Output kW Output kW Output kW Output kW
CR65
35 44.9 18.6 - - - -
40 69.1 45.2 19.3 - - -
45 93.8 69.7 45.6 20 - -
50 119.2 94.8 70.6 46.4 21 -
55 145.5 120.9 96.4 72 47.5 22.6
CR80
35 55.3 23 - - - -
40 85.8 55.8 23.8 - - -
45 116.7 86.6 56.5 24.7 - -
50 148.4 118.1 87.8 57.5 25.8 -
55 180.9 150.4 120 89.5 58.9 28.3
CR105
35 72.1 30 - - - -
40 110.8 72.6 31 - - -
45 150.4 111.7 73.3 32.2 - -
50 191.1 152.1 113.2 74.5 33.8 -
55 233.3 193.8 154.6 115.5 76.3 36.4
CR130
35 95.3 40.5 - - - -
40 146.3 95.9 41.7 - - -
45 198.3 147.6 97 43.2 - -
50 251.6 200.6 149.7 98.6 45.1 -
55 306.6 255.2 203.9 152.6 101 50.6
CR140
35 95.8 40.2 - - - -
40 147.2 96.3 41.5 - - -
45 199.6 148.3 97.2 43 - -
50 253.5 201.6 150.1 98.7 44.9 -
55 309 256.8 204.8 152.9 101 48.3
CR165
35 124.8 53.5 - - - -
40 191.6 125.6 55 - - -
45 259.6 193.2 126.9 56.9 - -
50 329 262.3 195.7 128.9 59.2 -
55 400.6 333.4 266.4 199.3 131.8 66.6
Technical Data
Performance Data
(1) Output kW refers to the condenser heat rejection.
Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C
-20°C
Maximum Ambient Air DB °C
+48
Optional On/O󰀨 Head Pressure Control
Minimum Ambient Air DB °C
-0°C
Maximum Ambient Air DB °C
+48
Operating Limit
(1) For conditions outside those quoted, please contact Airedale.
(2) Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.
CR12 - CR165 50/60HzCONDENSERS
19
Condenser Technical Manual 6666879 V2_02_2020