Mean Condensing Ambient
Temperature °C 25°C 30°C 35°C 40°C 45°C 48°C
Output kW Output kW Output kW Output kW Output kW Output kW
CR12
35 8.8 3.3 - - - -
40 13.8 8.8 3.4 - - -
45 19 14 8.9 3.6 - -
50 24.4 19.2 14.1 9.1 3.8 -
55 29.8 24.7 19.5 14.4 9.3 4.1
CR16
35 11.9 5 - - - -
40 18.2 12 5.2 - - -
45 24.7 18.4 12.1 5.4 - -
50 31.3 25 18.6 12.3 5.6 -
55 38.2 31.8 25.4 19 12.6 6.5
CR22
35 15.4 6.2 - - - -
40 24 15.5 6.4 - - -
45 32.8 24.2 15.7 6.7 - -
50 41.7 33.1 24.6 16 7 -
55 51 42.3 33.7 25.1 16.4 7.7
CR30
35 19.8 8.1 - - - -
40 30.6 20 8.4 - - -
45 41.7 30.9 20.2 8.7 - -
50 53.1 42.1 31.3 20.5 9.2 -
55 64.8 53.8 42.8 31.9 21 9.8
CR50
35 33.7 13.7 - - - -
40 52.6 34 14.2 - - -
45 71.7 53.1 34.4 14.8 - -
50 91.3 72.5 53.8 35.1 15.5 -
55 111.5 92.6 73.7 54.8 35.9 16.9
Technical Data
Performance Data
(1) Output kW refers to the condenser heat rejection.
Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C
-20°C
Maximum Ambient Air DB °C
+48
Optional On/O Head Pressure Control
Minimum Ambient Air DB °C
-0°C
Maximum Ambient Air DB °C
+48
Operating Limit
(1) For conditions outside those quoted, please contact Airedale.
(2) Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.
CR12 - CR165 50/60Hz CONDENSERS
18 Condenser Technical Manual 6666879 V2_02_2020