aldes H/E280 - Troubleshooting Further Issues; High Indoor Humidity & Condensation; Frost Formation on HRV;Ducts; Water Accumulation in HRV Bottom

aldes H/E280
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Residential HRV/ERV
41
Indoor air is too dry
(note: an HRV is
not a dehumidier,
however by
exchanging indoor
air with outdoor air,
it can reduce excess
indoor humidity if
the outdoor air is
drier).
• Dehumidistat wall control is set too
low
• HRV operang speed is too high
• Improperly balanced HRV
• Increase setpoint of dehumidistat.
• Operate HRV at low speed.
• Call a contractor to balance the HRV airows
• Add moisture to air with a humidier
Indoor air is too
humid and/or
condensaon is
forming on the inside
of windows
• Dehumidistat is set too high
• Obstructed supply or exhaust grilles
• Not enough exhaust capacity near
source of moisture
• HRV operang speed is too low
• Decrease the setpoint of the dehumidistat.
• Reduce sources of indoor humidity (steam,
wet clothes, plants, rewood) and excessive
temperature
• Operate HRV at high speed or use
connuous venlaon (not intermient or
ECO modes).
Frost is forming on
the HRV and/or
ducts connected to
the HRV
• HRV is not balanced
• HRV automac defrost funcon is
not working
• Leaky vapour barrier around
insulated duct
• Hole in exible duct
• Tape and seal all joints and duct connecons
• Repair any holes in exible duct
• Call contractor to balance the HRV and
verify defrost funconality
Water is
accumulang in the
boom of the HRV
• Obstructed drain line or drainage
pan.
• Improper connecon of drain
• HRV is not level
• Remove obstrucons or kinks in the
drainage tube
• Open HRV and check for material blocking
the drainage holes.
• Adjust the mounng chains or bracket so
that the HRV is level
HRV stays in high
speed aer the
20/40/60 minute
mer cycle is
complete
• One or more extracon ZRT dampers
remains open
• Timer in another bathroom is sll
acve
• Dehumidistat detected excess
humidity while mer was on
• Automac defrost cycle is running
based on cold outdoor temperature
• Check if wall control is set to a high speed
mode (dehumidistat, high-occupancy, etc...)
• Check the bathroom exhaust terminals to
ensure that the dampers are fully closed.
• Wait a maximum of 30 minutes for defrost
cycle to complete.