EasyManuals Logo

Alfa Laval T5 User Manual

Alfa Laval T5
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
Maintenance
Step 11
Open the plate pack b y letting the pressure plate glide on the
carrying bar. Usually it is not necessary to remove the plates
to clean them.
Caution!
To avoid hand injuries owing to sharp edg es, protective
gloves should always be worn when handling pl ates and
protection sheets.
Caution!
When opening the plate pack of the models M3, T2 and
TL3, be careful when m ovin g the pressure plate. Make
sure the pressure plate is posit ioned safely from the end
of the carrying bar.
A starlock ring (spare part no. 33500045-45) can be
attached to the end of the carrying bar to make sure the
pressure plate will not pass the end of the carrying bar.
If plates are to be numbered, do this before removing the plates.
Plates ne ed not be removed if cleaning is done using only water,
i.e. without a cleaning agent.
Warning!
The plate pack may sti ll contain a small residua l amount
of liquid after draining. Depending on the type of
product and type of installation, special arrangements,
e.g. drainage box, may be necessary to avoid injury to
personnel and damage to equipment.
Document ID La nguage Edition
3490010217 EN 2016-06 Instruction Ma nual - Plate Heat Exchan gers 23
EN

Other manuals for Alfa Laval T5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Alfa Laval T5 and is the answer not in the manual?

Alfa Laval T5 Specifications

General IconGeneral
BrandAlfa Laval
ModelT5
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals