144 Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
See Table 55…Table 60 for reference data related to input and output data.
Table 55 - Input Data 1732ES-IB16 Modules
Instance Hex
(decimal)
Connection Type Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
205 (517) Safety and standard 0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
225 (549) Safety and standard 0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
2Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
300 (768) Standard only 0 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Input Power
Error
315 (789) Safety and standard 0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
2 Combined
Safety In
Status
Reserved Input Power
Error
(1)
Reserved Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
335 (821) Safety and standard 0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
2Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
4 Reserved Reserved Input Power
Error
(1)
Reserved Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
365 (869) Safety and standard 0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
2Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
4 Test Output 7
Status
Test Output 6
Status
Test Output 5
Status
Test Output 4
Status
Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
5 Test Output
15 Status
Test Output
14 Status
Test Output
13 Status
Test Output
12 Status
Test Output
11 Status
Test Output
10 Status
Test Output 9
Status
Test Output 8
Status
6 Reserved Reserved Input Power
Error
(1)
Reserved Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
385 (901) Standard only 0 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Input Power
Error
1 Test Output 7
Status
Test Output 6
Status
Test Output 5
Status
Test Output 4
Status
Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
2 Test Output
15 Status
Test Output
14 Status
Test Output
13 Status
Test Output
12 Status
Test Output
11 Status
Test Output
10 Status
Test Output 9
Status
Test Output 8
Status
(1) This data is only diagnostic data. This data does not have safety integrity.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1732ES-IB8XOBV4 and is the answer not in the manual?

Allen-Bradley 1732ES-IB8XOBV4 Specifications

General IconGeneral
BrandAllen-Bradley
Model1732ES-IB8XOBV4
CategoryControl Unit
LanguageEnglish

Related product manuals