POINT I/O 4 Channel Analog Current Output Module 13
Publication 1734-IN034C-EN-E - August 2016
Remove a Mounting Base
To remove a mounting base, you must remove any installed module, and the module
installed in the base to the right. Remove the Removable Terminal Block, if wired.
1. Unlatch the RTB handle on the I/O module.
2. Pull on the RTB handle to remove the Removable Terminal Block.
3. Press on the module lock on the top of the module.
4. Pull on the I/O module to remove from the base.
5. Repeat steps 1, 2, 3 and 4 for the module to the right.
6. Use a small bladed screwdriver to rotate the orange base locking screw to a
vertical position. This releases the locking mechanism.
7. Lift straight up to remove.
Install a 1734-TOPS Base
1. Position the base vertically above the installed units, such as an adapter, power
supply, or existing module.
2. Slide the base down, allowing the interlocking side pieces to engage the adjacent
installed unit.
3. Press firmly to seat the base on the DIN rail until the base snaps into place.
4. Verify that the DIN-rail locking screw is in a horizontal, locked position before
inserting an I/O module.
Remove a 1734-TOPS Base
1. To remove a wiring base from the DIN rail, you must remove the module
installed to the right of the base.
2. Squeeze the module locking mechanism of the module to the right of the base,
pulling up to remove the module.
3. Turn the orange locking screw to a vertical position to unlock the base from the
DIN rail.
4. Slide the base up to release it from its mating units.