POINT I/O 4 Channel Analog Current Output Module 17
Publication 1734-IN034C-EN-E - August 2016
Specifications
Output Specifications
Attribute Value
Number of outputs 4 analog, single-ended, non-isolated
Resolution current 16 bits – over 0…21 mA
0.32 μA/cnt
Output current terminal 0 mA output until communication established
4…20 mA user configurable
0…20 mA user configurable
Absolute accuracy
(1)
current
terminal, min
(1)
Includes offset, gain, non-linearity and repeatability error terms.
0.4% (0.1% if calibrated)
Accuracy drift w/temperature
current terminal
<50 ppm/°C
Resistive load on mA output 0…750 Ω
Conversion type Digital to analog converter
Conversion rate 1 μs
Data format Signed integer
Calibration Factory calibrated
Step response to 63% of
value, max
160 μs
Surge current 2 A for 10 ms, repeatable every 3 s
Status indicators, logic side 1 green/red network status
1 green/red module status
4 green/red output status
Refer to Publication 1734-SG001 for information on breaking the field
power distribution bus. Refer to sections “When to Use the Field Power
Distributor” and “When to Use the Expansion Power Unit”.