36 Rockwell Automation Publication 1756-UM058G-EN-P - November 2012
Chapter 2 Digital I/O Operation in the ControlLogix System
To prevent other owner-controllers from receiving potentially erroneous data, use
these steps when changing a module’s configuration in a multiple owner scenario
while online.
1. For each owner-controller, inhibit the connection to the module either in
the software on the Connection tab or the message dialog box warning you
of the multiple owner condition.
2. Make the appropriate configuration data changes in the software. For more
information about using RSLogix 5000 software to change the
configuration, see Chapter
7.
3. Repeat step 1
and step 2 for all owner-controllers, making the exact same
changes in each.
4. Clear the Inhibit checkbox in each owner-controller configuration.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1756-IA8D and is the answer not in the manual?

Allen-Bradley 1756-IA8D Specifications

General IconGeneral
Number of Inputs8
Connection TypeRemovable Terminal Block
Product TypeInput Module
Module LocationIn ControlLogix chassis
Input TypeSinking
Operating Temperature0°C to 60°C (32°F to 140°F)
Storage Temperature-40 to 85 °C
Relative Humidity5% to 95% (non-condensing)
CompatibilityControlLogix

Related product manuals