180 Rockwell Automation Publication 1756-UM001M-EN-P - February 2012
Chapter 11 Using the PhaseManager Tool
Manually Change States
With RSLogix 5000 software, you can manually change an equipment phase. To
manually change a PhaseManager state, perform this procedure.
1. Open the Equipment Phase Monitor.
2. Take ownership of the equipment phase by clicking Owners and clicking
Yes.
3. Click the command that initiates the state you need (for example, Start or
Reset).
4. After you have finished manually changing the state, click Owners to
release your ownership.
PhaseManager Tool versus
Other State Models
This table compares PhaseManager state models to other state models.
Table 48 - PhaseManager Tool and Other State Models
PhaseManager Tool S88 PackML
Resetting…Idle Idle Starting…Ready
Running…Complete Running…Complete Producing
Subroutines or breakpoints Pausing…Paused Standby
Holding…Held Holding…Held Holding…Held
Restarting Restarting None
Stopping…Stopped Stopping…Stopped Stopping…Stopped
Aborting…Aborted Aborting…Aborted Aborting…Aborted

Table of Contents

Other manuals for Allen-Bradley ControlLogix L7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ControlLogix L7 and is the answer not in the manual?

Allen-Bradley ControlLogix L7 Specifications

General IconGeneral
BrandAllen-Bradley
ModelControlLogix L7
CategoryController
LanguageEnglish

Related product manuals