1785-UM022B-EN-P - February 2002
D-10 ControlNet I/O Map-Entry Status Words and Error Codes
65530 0xFFFA MODULE DECLARED INVALID
LENGTH
A communication error between the
adapter and the module caused the
transfer to be aborted.
Make sure that the module is
properly seated in the correct slot of
the target node.
Make sure that the adapter’s power
supply is providing the proper
voltage.
The target slot contains the wrong
module type.
Insert the proper module in the
correct slot of the target node.
An incorrect module or slot was
entered in the map table.
Edit the I/O map table to show the
correct module type and slot.
65531 0xFFFB INVALID READ DATA A communication error between the
adapter and the module caused the
transfer to be aborted.
Make sure that the module is
properly seated in the correct slot of
the target node.
Make sure that the adapter’s power
supply is providing the proper
voltage.
The target slot contains the wrong
module type.
Insert the proper module in the
correct slot of the target node.
An incorrect module or slot was
entered in the map table.
Edit the I/O map table to show the
correct module type and slot.
65532 0xFFFC INVALID WRITE DATA A communication error between the
adapter and the module caused the
transfer to be aborted.
Make sure that the module is
properly seated in the correct slot of
the target node.
Make sure that the adapter’s power
supply is providing the proper
voltage.
The target slot contains the wrong
module type.
Insert the proper module in the
correct slot of the target node.
An incorrect module or slot was
entered in the map table.
Edit the I/O map table to show the
correct module type and slot.
65533 0xFFFD DATA TABLE TOO SMALL The processor data table is too small
to hold the data to be transferred.
Increase the size of the data table to
accommodate the transfer length.
Decimal
Code
Hex. Code Error Message Explanation/Possible Cause(s) Possible Corrective Action(s)

Table of Contents

Other manuals for Allen-Bradley ControlNet PLC-5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ControlNet PLC-5 and is the answer not in the manual?

Allen-Bradley ControlNet PLC-5 Specifications

General IconGeneral
BrandAllen-Bradley
ModelControlNet PLC-5
CategoryController
LanguageEnglish

Related product manuals