Rockwell Automation Publication 2080-UM002K-EN-E - March 2019 311
Troubleshooting Appendix E
0xF0878 Recoverable An index used to access a bit is beyond the
boundaries of the data type it is used on.
Perform the following:
1. See Corrective Actions for Recoverable Faults on page 313.
2. Correct the program to ensure that there is no index used to access
a bit beyond the boundaries of the data type.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF880 Recoverable A data conversion error occurred. Perform the following:
1. See Corrective Actions for Recoverable Faults
on page 313.
2. Correct the program to ensure that there is no data conversion error.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF888 Recoverable The call stack of the controller cannot support the
sequence of calls to function blocks in the current
project. Too many blocks are within another
block.
Perform the following:
• See Corrective Actions for Recoverable Faults on page 313.
• Change the project to reduce the quantity of blocks being called
within a block.
0xF898 Recoverable An error occurred in the user interrupt
configuration for the plug-in I/O module.
Perform the following:
• See Corrective Actions for Recoverable Faults
on page 313.
• Correct the user interrupt configuration for plug-in I/O module in the
user program to match that of the actual hardware configuration.
0xF8A0 Recoverable The TOW parameters are invalid. Perform the following:
1. See Corrective Actions for Recoverable Faults on page 313.
2. Correct the program to ensure that there are no invalid parameters.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF8A1 Recoverable The DOY parameters are invalid. Perform the following:
1. See Corrective Actions for Recoverable Faults
on page 313.
2. Correct the program to ensure that there are no invalid parameters.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
List of Error Codes for Micro800 controllers
Error Code Fault Type Description Recommended Action