EasyManuals Logo

Allen-Bradley micrologix 1500 Reference Manual

Allen-Bradley micrologix 1500
424 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
Publication 1762-RM001C-EN-P
6-16 Using High-Speed Outputs
PTO Jog Continuous (JC)
The PTO JC (Jog Continuous) bit instructs the PTO sub-system to generate
continuous pulses. The frequency generated is defined by the Jog
Frequency parameter in the PTO function file. Jog Continuous operation
is only possible under the following conditions:
PTO sub-system in idle
Jog Pulse not active
Enable not active
The JC bit operates as follows:
Set (1) - Instructs the PTO sub-system to generate continuous Jog
Pulses
Cleared (0) - The PTO sub-system does not generate Jog Pulses
When the Jog Continuous bit is cleared, the current output pulse is
truncated.
PTO Jog Continuous Status (JCS)
The PTO JCS (Jog Continuous Status) bit is controlled by the PTO
sub-system. It can be used by an input instruction on any rung within the
control program to detect when the PTO is generating continuous Jog
Pulses. The JCS bit operates as follows:
Set (1) - Whenever a PTO instruction is generating continuous Jog
Pulses
Cleared (0) - Whenever a PTO instruction is not generating
continuous Jog Pulses.
Sub-Element
Description
Address Data Format Range Type User Program
Access
JC - Jog Continuous PTO:0/JC bit 0 or 1 control read/write
Sub-Element Description Address Data
Format
Range Type User Program
Access
JCS - Jog Continuous Status PTO:0/JCS bit 0 or 1 status read only

Table of Contents

Other manuals for Allen-Bradley micrologix 1500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley micrologix 1500 and is the answer not in the manual?

Allen-Bradley micrologix 1500 Specifications

General IconGeneral
Processor Type16-bit
Programming LanguageLadder Logic
MountingDIN rail or panel mount
Programming SoftwareRSLogix 500
Communication PortsRS-232
Power Supply24V DC
Operating Temperature0°C to 55°C (32°F to 131°F)
Controller TypeProgrammable Logic Controller (PLC)