Data Logging (MicroLogix 1500 1764-LRP Processor only) 22-7
Enter the following information:
4. After entering all the information for the data log queue, click on OK.
The queue is added to the Data Log Que window with a
corresponding queue number. This is the queue number to use in the
DLG instruction.
Data Log Queue
Configuration Parameter
Description
Number of Records Defines the number of records (data sets) in the queue.
Separator Character Choose the character to act as the separator for the data in this
queue (tab, comma, or space). The separator character may be the
same or different for each queue configured.
Date Stamp (optional)
if selected, the date is recorded in mm/dd/yyyy format
(1)
.
(1) If the real-time clock is not present on the controller and Date Stamp and Time Stamp are selected (enabled), the date
is recorded as 00/00/0000 and the time as 00:00:00.
Time Stamp (optional)
if selected, the time is recorded in hh:mm:ss format
(1)
.
Address to Log Enter the address of an item to be recorded and click on Accept to
add the address to the Current Address List. The address can be
any 16 or 32-bit piece of data.
Current Address List This is the list of items to be recorded. Record size can be up to 80
bytes. You can use the Delete button to remove items from this list.
See page 22-3 for information on record size.
A record consists of configured Date Stamp, Time Stamp, Current Address List, and Separator
Characters.

Table of Contents

Other manuals for Allen-Bradley micrologix 1500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley micrologix 1500 and is the answer not in the manual?

Allen-Bradley micrologix 1500 Specifications

General IconGeneral
Processor Type16-bit
Programming LanguageLadder Logic
MountingDIN rail or panel mount
Programming SoftwareRSLogix 500
Communication PortsRS-232
Power Supply24V DC
Operating Temperature0°C to 55°C (32°F to 131°F)
Controller TypeProgrammable Logic Controller (PLC)

Related product manuals