5-16 Using the High-Speed Counter
Count Up (CU)
The CU (Count Up) bit is used with all of the HSCs (modes 0 to 7). If the
CE bit is set, the CU bit is set (1). If the CE bit is clear, the CU bit is cleared
(0).
HSC Mode (MOD)
The MOD (Mode) variable sets the High-Speed Counter to one of 8 types
of operation. This integer value is configured through the programming
device and is accessible in the control program as a read-only variable.
Description Address Data Format
HSC Modes
(1)
(1) For Mode descriptions, see HSC Mode (MOD) on page 5-16.
Type User Program Access
CU - Count Up HSC:0/CU bit 0 to 7 status read only
Description Address Data Format Type User Program Access
MOD - HSC Mode HSC:0.MOD word (INT) control read only
Table 5.3 HSC Operating Modes
Mode
Number
Type
0 Up Counter - The accumulator is immediately cleared (0) when it reaches the high
preset. A low preset cannot be defined in this mode.
1 Up Counter with external reset and hold - The accumulator is immediately cleared
(0) when it reaches the high preset. A low preset cannot be defined in this mode.
2 Counter with external direction
3 Counter with external direction, reset, and hold
4 Two input counter (up and down)
5 Two input counter (up and down) with external reset and hold
6 Quadrature counter (phased inputs A and B)
7 Quadrature counter (phased inputs A and B) with external reset and hold

Table of Contents

Other manuals for Allen-Bradley micrologix 1500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley micrologix 1500 and is the answer not in the manual?

Allen-Bradley micrologix 1500 Specifications

General IconGeneral
Processor Type16-bit
Programming LanguageLadder Logic
MountingDIN rail or panel mount
Programming SoftwareRSLogix 500
Communication PortsRS-232
Power Supply24V DC
Operating Temperature0°C to 55°C (32°F to 131°F)
Controller TypeProgrammable Logic Controller (PLC)