18 POINT I/O EtherNet/IP Adapter
Publication 1734-IN042F-EN-P - November 2018
General Specifications
Attribute Value
Indicators 3 red/green status indicators (on CPU):
– Module status
– Network status
– POINTBus status
1 green status indicator on CPU:
– Network activity
2 green power supply status indicators on DC-DC Converter:
– System power (5V DC to POINTBus Out)
– Field power (24V DC from Field In)
Power consumption, max 10.4 W @ 28.8V DC
Power dissipation, max 5.2 W @ 28.8V DC
Thermal dissipation, max 17.75 BTU/hr @ 28.8V DC
Isolation voltage 50V (continuous), Reinforced Insulation Type, between all circuits.
Type tested at 500V AC for 60 s
Field power supply 10...28.8V DC @ 10A
Field power output 10...28.8V DC @ 9A
Module input 10...28V DC @ 1000 mA
POINTBus output, max 5V DC @ 1.0A
Dimensions (HxWxD), approx. 76.2 x 54.9 x 133.4 mm (3.0 x 2.16 x 5.25 in.)
Enclosure type rating None (open-style)
Terminal base screw torque 0.8 Nm (7 lb-in)
Weight, approx. 255 g (0.56 lb)
Wiring category
(1)
,
(2)
1 – on power ports
1 – on communications ports
Wire Size Power connections:
0.34... 2.1 mm
2
(22...14 AWG) solid or stranded copper wire rated
@ 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max or
90
°C (194 °F) for ControlLogix®.
Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e
min cable according to TIA 568-B.1 or Category 5 cable according
to ISO/IEC 24702.
North American temp code T4A
ATEX Temp Code T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-IN041.