Rockwell Automation Publication 520-UM001G-EN-E - September 2014 125
Programming and Parameters Chapter 3
Advanced Program Group (continued)
A553 [Program Lock Mod] Related Parameter(s): A552
Determines the lock mode used in parameter A552 [Program Lock]. When set to 2 or 3, A552 [Program Lock] is added to the custom group to allow unlocking of parameters.
Options 0 “Full Lock” (Default) All parameters are locked except [Program Lock].
1 “Keypad Lock” All parameters are locked except [Program Lock] from keypad access but can still be accessed over communications.
2 “Custom Only” All parameters are locked and hidden except custom group and [Program Lock].
3 “KeyPd Custom All parameters are locked and hidden except custom group and [Program Lock] from keypad access but can still be accessed over
communications.
A554 [Drv Ambient Sel]
Sets the maximum expected ambient of the drive when used above 50 °C. When ambient temperature is above 50 °C, the drive will apply necessary current derating.
Options 0“Normal (Default)
1“55C
2“60C
3 “65C +Fan Kit” Fan kit required.
4 “70C +Fan Kit”
A555 [Reset Meters] Related Parameter(s): b019, b021, b022, b023, b024,
b025
, b026, d362, d363
Resets the values stored in the parameters that track fault times and energy usage.
Options 0 “Ready/Idle” (Default)
1 “Reset Meters” Resets kWh, MWh, Accum kWh, Cost, and CO2 Sav parameter values.
2 “Reset Time” Resets min, hr, and x10 hr.
A556 [Text Scroll]
Sets the scrolling speed of the text in the LCD display.
Options 0“Off No scroll.
1“Low Speed
2 “Mid Speed” (Default)
3 “High Speed”
A557 [Out Phas Loss En]
Enable/disable output phase loss detection.
Options 0“Disable (Default)
1“Enable
ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in an inappropriate application. Do not use this function without
considering applicable local, national and international codes, standards, regulations or industry guidelines.
A558 [Positioning Mode]
Stop drive before changing this parameter.
PowerFlex 525 only.
Defines the positioning transition mode used for the position steps.
Options 0 Time Steps” (Default) Steps based on time.
1 “Preset Input” Preset inputs directly commands a given step.
2 “Step Logic Use Step Logic Commands. Always start from Step 0.
3 “Preset StpL Use Preset Inputs to determine starting step then Step Logic commands.
4 “StpLogic-Lst” Use Step Logic commands from last Step Logic step at last drive stop.
PF 525

Table of Contents

Other manuals for Allen-Bradley PowerFlex 523

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 523 and is the answer not in the manual?

Allen-Bradley PowerFlex 523 Specifications

General IconGeneral
Frequency50/60 Hz
DimensionsVaries by model
WeightVaries by model
Output Voltage0 to Input Voltage
Power Rating0.4-22 kW
Control MethodSensorless Vector Control
EnclosureIP20
CommunicationEtherNet/IP
Operating Temperature-20 to 50°C (-4 to 122°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Relative Humidity5% to 95% (non-condensing)
Input Voltage200-240V AC, 380-480V AC
Horsepower0.5…30 Hp