98 Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3 Programming and Parameters
Communications Group (continued)
C146 [EN Flt Cfg Ref] Related Parameter(s): C143, C144
32 bit parameter.
PowerFlex 525 only.
Sets the Reference data that is sent to the drive if any of the following is true:
C143 [EN Comm Flt Actn] is set to 4 “Send Flt Cfg” and communications are disrupted.
C144
[EN Idle Flt Actn] is set to 4 “Send Flt Cfg” and the scanner is put into Program or Test mode.
Values Default: 0
Min/Max: 0/50000
Display: 1
PF 525
C147 [EN Flt Cfg DL 1]
C148 [EN Flt Cfg DL 2]
C149 [EN Flt Cfg DL 3]
C150 [EN Flt Cfg DL 4]
PowerFlex 525 only.
Sets the Ethernet Datalink Input data that is sent to the drive if any of the following is true:
C143 [EN Comm Flt Actn] is set to 4 “Send Flt Cfg” and communications are disrupted.
C144
[EN Idle Flt Actn] is set to 4 “Send Flt Cfg” and the scanner is put into Program or Test mode.
Values Default: 0
Min/Max: 0/65535
Display: 1
PF 525
C153 [EN Data In 1]
C154 [EN Data In 2]
C155 [EN Data In 3]
C156 [EN Data In 4]
PowerFlex 525 only.
Datalink parameter number whose value is written from the embedded EtherNet/IP data table. This parameter cannot be changed when an I/O connection is established through the
drives embedded EtherNet/IP port.
Values Default: 0
Min/Max: 0/800
Display: 1
PF 525
C157 [EN Data Out 1]
C158 [EN Data Out 2]
C159 [EN Data Out 3]
C160 [EN Data Out 4]
PowerFlex 525 only.
Datalink parameter number whose value is read from the embedded EtherNet/IP data table. This parameter cannot be changed when an I/O connection is established through the
drives embedded EtherNet/IP port.
Values Default: 0
Min/Max: 0/800
Display: 1
PF 525

Table of Contents

Other manuals for Allen-Bradley PowerFlex 523

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 523 and is the answer not in the manual?

Allen-Bradley PowerFlex 523 Specifications

General IconGeneral
Frequency50/60 Hz
DimensionsVaries by model
WeightVaries by model
Output Voltage0 to Input Voltage
Power Rating0.4-22 kW
Control MethodSensorless Vector Control
EnclosureIP20
CommunicationEtherNet/IP
Operating Temperature-20 to 50°C (-4 to 122°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Relative Humidity5% to 95% (non-condensing)
Input Voltage200-240V AC, 380-480V AC
Horsepower0.5…30 Hp