EasyManuals Logo

Allen-Bradley PowerFlex 70 Installation Instructions

Allen-Bradley PowerFlex 70
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
Rockwell Automation Publication 20A-IN009E-EN-P - January 2015 7
PowerFlex 70 Adjustable Frequency AC Drive
Output Contactor Precaution
ATTENTION: The adjust freq” portion of the bus regulator function is useful for
preventing nuisance overvoltage faults that result from aggressive
decelerations, overhauling loads, and eccentric loads. It forces the output
frequency to be greater than commanded frequency while the drives bus
voltage is increasing towards levels that can cause a fault; however, it can also
cause either of the following two conditions to occur.
Fast positive changes in input voltage (more than a 10% increase within 6
minutes) can cause uncommanded positive speed changes; however an F25
“OverSpeed Limit” fault occurs if the speed reaches P82 [Max Speed] + P83
[Overspeed Limit]. If this condition is unacceptable, take theses actions;
1) limit supply voltages within the specification of the drive and,
2) limit fast positive input voltage changes to less than 10%. Without taking
such actions, if this operation is unacceptable, the “adjust freq” portion of the
bus regulator function must be disabled (see parameters 161 [Bus Reg Mode A]
and 162 [Bus Reg Mode B]).
Actual deceleration times can be longer than commanded deceleration times;
however, a “Decel Inhibit” fault is generated if the drive stops decelerating
altogether. If this condition is unacceptable, the “adjust freq” portion of the bus
regulator must be disabled (see parameters 161 [Bus Reg Mode A] and 162
[Bus Reg Mode B]). In addition, installing a properly sized dynamic brake
resistor provides equal or better performance in most cases.
Note: These faults are not instantaneous and have shown test results that take
2...12 seconds to occur.
ATTENTION: To guard against drive damage when using output contactors,
the following information must be read and understood. One or more output
contactors can be installed between the drive and motor(s) for disconnecting
or isolating certain motors/loads. If a contactor is opened while the drive is
operating, power is removed from the respective motor, but the drive
continues to produce voltage at the output terminals. In addition, reconnecting
a motor to an active drive (by closing the contactor) could produce excessive
current that can cause the drive to fault. If any of these conditions are
determined to be undesirable or unsafe, wire an auxiliary contact on the
output contactor to a drive digital input that is programmed as “Enable.” With
the drive Enable input wired to the output contactor, the drive will coast-to-
stop (cease output) whenever the output contactor is opened.
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Other manuals for Allen-Bradley PowerFlex 70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 70 and is the answer not in the manual?

Allen-Bradley PowerFlex 70 Specifications

General IconGeneral
Input Voltage200-240V AC, 380-480V AC, 500-600V AC
Frequency Range0 - 400 Hz
Humidity5% to 95% non-condensing
Output Voltage0 to Input Voltage
Control MethodsSensorless Vector Control
CommunicationsEthernet/IP, DeviceNet, ControlNet
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Ground Fault
Operating Temperature0°C to 50°C (32°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Enclosure RatingIP20, NEMA Type 1

Related product manuals