Reference Section
Drive Status Indicators
Table 41 - PowerFlex 753 Status Indicator Descriptions
Name Color State Description
STS
(Status)
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing Drive is not running, a start inhibit condition exists and the drive cannot be started.
See pa
rameter 933 [Start Inhibits].
Steady A type 1 (user configurable) alarm exists. If the drive is stopped, it is prevented from
starti
ng until the alarm condition is cleared. If the drive is running, it continues to
run but cannot restart until the alarm condition is cleared.
See parameters 959 [Alarm Status A]
and 960 [Alarm Status B].
Red Flashing A major fault has occurred. Drive stops. Drive cannot be started until fault condition
is clea
red. See parameter 951 [Last Fault Code].
Steady A non-resettable fault has occurred.
Red /
Y
e
llow
Flashing
Alternately
A minor fault has occurred. When running, the drive continues to run. System is
brought to a stop under system control. Fault must be cleared to continue. Use
parameter 950 [Minor Flt Cfg] to enable. If not enabled, acts like a major fault.
Yellow /
Green
Flashing
Alte
rnately
When running, a type 1 alarm exists.
See parameters 959 [Alarm Status A] and 960 [Alarm Status B].
Green /
Red
Flashing
Alte
rnately
Drive is flash updating.
Table 42 - PowerFlex 755 Status Indicator Descriptions
Name Color State Description
STS
(Status)
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing Drive is not running, a type 2 (non-configurable) alarm condition exists and the
d
rive cannot be started. See parameter 961 [Type 2 Alarms].
Steady A type 1 (user configurable) alarm exists. If the drive is stopped, it is prevented from
starti
ng until the alarm condition is cleared. If the drive is running, it continues to
run but cannot restart until the alarm condition is cleared.
See parameters 959 [Alarm St
atus A] and 960 [Alarm Status B].
Red Flashing A major fault has occurred. Drive stops. Drive cannot be started until fault condition
is cl
eared. See parameter 951 [Last Fault Code].
Steady A non-resettable fault has occurred.
Red /
Y
e
llow
Flashing
Alternately
A minor fault has occurred. When running, the drive continues to run. System is
brought to a stop under system control. Fault must be cleared to continue. Use
parameter 950 [Minor Flt Cfg] to enable. If not enabled, acts like a major fault.
Yellow /
Gr
een
Flashing
Alternately
When running, a type 1 alarm exists.
See parameters 959 [Alarm St
atus A] and 960 [Alarm Status B].
Green /
Red
Flashing
Alte
rnately
Drive is flash updating.
ENET Unlit Off Embedded EtherNet/IP is not properly connect
ed to the network or needs an IP
address.
Red Flashing An EtherNet/IP connection has timed out.
Steady Adapter failed the duplicate IP address detection test.
Red /
G
reen
Flashing
Alternately
Adapter is performing a self-test.
Green Flashing Adapter is properly connected but is not communicating with any de
vices on the
network.
Steady Adapter is properly connected and communicating on the network.
LINK Unlit Off Adapter is not powered or is not transmitting on the network.
Green Flashing Adapter is properly connected and transmitting data packets on the network.
Steady Adapter is properly connected but is no
t
transmitting on the network.

Other manuals for Allen-Bradley PowerFlex 755

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 755 and is the answer not in the manual?

Allen-Bradley PowerFlex 755 Specifications

General IconGeneral
CategoryAC Drive
Amperage2.2…1470 A
Output Voltage0 to Input Voltage
Output Current2.2…1470 A
EnclosureIP20, IP30, IP54
CommunicationsEtherNet/IP, ControlNet, DeviceNet
I/ODigital, Analog, Encoder, Relay
SafetySafe Speed Monitor
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Short Circuit, Ground Fault, Overtemperature
Operating Temperature-10°C to 50°C (14°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Humidity5…95% noncondensing
AltitudeUp to 1000m (3300ft) without derating
Voltage200-240V AC, 380-480V AC, 500-600V AC, 690V AC
Input Voltage200-240V AC, 380-480V AC, 500-600V AC, 690V AC
Control MethodSensorless Vector