Loading...
SLC 500™ Fixed Hardware Style Controllers 7
Publication 1747-IN008B-MU-P
Controller Spacing
Follow the recommended controller orientation and minimum spacing shown below
to allow for convection cooling within the enclosure. Air in the enclosure must be
kept within the range of 0°C to +60°C (+32°F to +140°F).
Mounting the 2-Slot Expansion Chassis (Optional)
The expansion chassis mounts on the right side of the fixed controller.
1. Align the mounting inserts of the expansion chassis with the mounting slots of
the controller. Slide the expansion chassis forward until the back of the expansion
chassis is flush with the fixed controller and the connector on the expansion
circuit board is mated with the connector in the controller.
A
B
A
B
TOP
SIDESIDE
BOTTOM
A. Greater than 101.6 mm (4 in.)
B. Greater than 152.4 mm (6 in.)
Enclosure
AB Drives

Table of Contents