P1: Start/Stop Control
Function
code
Function
Name
LCD
Display
Range of settings
Default
Change
MODBUS
Address
P1.00
Starting
mode
Starting
mode
0: Start directly
1: Brake first and
then start at start
frequency
2: Start after speed
tracking (the
mode is only valid
for the motor of
35R5GB/37R5PB
or above)
Note: the startup
includes power on,
power recovery after
an instantaneous off,
external fault reset,
and restart after
coast to stop.
0
0200
P1.01
Starting
frequenc
y
Starting
frequency
0.1060.00Hz
0.50Hz
0201
P1.02
Starting
frequenc
y holding
time
Starting
holding
time
0.010.0s
0.0s
0202
P1.03
DC
injection
braking
current at
start
Brake
current at
start
Type G: 0.0
100.0% of ac drive
rated current
Type P: 0.080.0%
of ac drive rated
current
0.0%
0203
P1.04
DC
injection
braking
time at
start
Brake
time at
start
0.030.0s
0.0s
0204
P1.05
Acc/Dec
mode
Acc/Dec
mode
0: Linearity
1: S-curve
2: (Reserved)
3: (Reserved)
0
0205