EasyManua.ls Logo

Alpha ARES 150 Tec - Page 40

Alpha ARES 150 Tec
59 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
1
Follow this procedure to adjust the other modules as well.
If the measured ow rate is too low, make sure the supply and draining
systems (the supply and draining pipes) are not obstructed.
If they are not obstructed, make sure the burner and/or exchanger
are not dirty.
When replacing the gas valve or
having diculty with ignition:
Screw general adjusting screw "A" on clockwise until
it stops, then unscrew by 7 revolutions.
Check boiler ignition. If it does not start up unscrew
screw "A" by one more revolution, then try to start it
up again. If the boiler does not start up again, follow
the operations described above until the boiler does
start up again.
At this point adjust the burner as previously
illustrated.
ATTENTION
Calibrate the VGs (Gas Valves) in the heating control
unit referring to the procedures below.
Calibration of the VGs
must be carried out with the ue pressure = 0 Pa;
for this reason:
- open the inspection door of ue pipe 1;
aer calibration, close the inspection door.
3) Completing basic calibration
-
Check CO
2
values at the minimum and maximum ow rate
.
-
Touch up if necessary
.
For smooth operation, calibrate the CO
2
values taking
care to observe the values in the table.
- Close the cap (2 - 3) for the ue inspection point back up (1)
NOTE: Do not force the adjusting screw limit switch
limits.

Related product manuals