EasyManua.ls Logo

Alstom iSTAT M232 - Instrumentation; Measurements

Alstom iSTAT M232
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual M2x2/EN M/F
iSTAT M2x2
Page 15
Connection Type
TABLE 8-2 : BASIC
Parameter Unit
MEASUREMENTS
1b 3b 3u 4b 4u
MD current I
1
I1 A
MD current I
2
I2 A ×
MD current I
3
I3 A ×
MD active power P (positive) P+ W
MD active power P (negative) P W
MD reactive power QL Q var
MD reactive power QC Q var
Max. values MD
MD apparent power S S VA
Key –measured, calculated, × not supported
NOTE: For 3b and 3u connection mode, only phasetophase voltages are
measured. Because of that, factor 3 is applied to calculation of
quality considering nominal phase voltage.
For 4u connection mode measurements support is same as for 1b.
7.2 Power mode
The po
wer mode is used for the signing of power measurements. The user cannot set the
M2x2 power mode. It is defined as follows:
When displaying active power, a positive sign indicates export power
(a consumer) whilst a negative sign indicates import power (a generator).
When displaying reactive power, a coil symbol indicates an inductive load
(a consumer) whilst a capacitor symbol indicates a capacitive load
(a generator).
7.3 Operating energy quadrants
The
operating energy quadrants are used to determine which types of energy are added to
the energy counters. The user may modify the operating energy quadrants via the remote
communications interface or by using the front menu and buttons.

Table of Contents

Related product manuals