3 - INSTALLATION
3.7 - Electrical Connections
To make the electrical connections to the M32
flywheel:
1. Run the following conduits and wiring to the M32
flywheel and secure them to the Electronics
Enclosure using watertight connectors:
- Connect a 1” flex conduit to the bottom port of
the Electronics Enclosure. This conduit will
contain one red and one black copper wire (size
14-8AWG), and one bare grounding copper
wire, size 14-4AWG.
- Connect a 3/4” flex conduit to the middle port
of the Electronics Enclosure. This conduit will
contain one white, one black, and one green
copper wire, size 22-12AWG.
- Connect a 1 1/4” flex conduit to the top port of
the Electronics Enclosure. This conduit will
contain two Cat6a Ethernet cables.
Figure 16: Flex conduits connected to
Electronics Enclosure
Note: Conduit must be a watertight type
approved for use in your local
jurisdiction. The specific conduit type
and routing (such as above- or below-
grade) is beyond the scope of this
manual.