TR-2100 User Manual  64 
Recording (Transient) 
Recording resolution    16 bits (65536 levels) 
 
Dynamic range    96.3 dB 
 
Recording accuracy    +/- 1 LSB 
 
Sample rate      Up to 19,200 per sec. at 50 Hz 
        Up to 23,040 per sec. at 60 Hz 
    COMTRADE rates supported 
    Analogues and digitals can have different rates 
 
Pre-fault time      2 - 500 cycles 
 
Post-fault time  Fault length will extend as long as a trigger condition 
exists 
        Minimum is 8 - 100 cycles 
 
Safety window      Recording time after trigger: 4 - 16 cycles 
 
Maximum record length  1 - 30 sec. (This prevents memory filling with a 
continuous trigger) 
 
Synchronization  All analogue channels sampled together and time 
tagged to better than +/- 100 ns (if GPS option is used) 
 
Programmable Features  Sample rates 
Pre, max & min post fault times 
    Safety window 
    Maximum record length 
Trigger level and polarity 
Trigger enable 
Time and date 
Channel labels 
Local time offset 
 
Configuration Switches  Number of analogue channels 
    Number of digital channels 
System frequency (50/60) 
    Printer connected 
    Modem connected 
    Network connected 
    Cross trigger enabled