TR-2100 User Manual 81
DNP v3.00 Device Profile Document
The purpose of this document is to describe the specific implementation of the Distributed
Network Protocol (DNP) 3.0 within the TR-2100 Transient Recorder. This document, in
conjunction with the DNP 3.0 Basic 4 Document Set, and the DNP Subset Definitions
Document, provides complete information on how to communicate with the TR-2100 via the
DNP 3.0 protocol.
The TR-2100 uses the Triangle MicroWorks™, Inc. DNP 3.0 Slave Source Code
Library Version 2.19. This implementation of DNP 3.0 is fully compliant with DNP 3.0
Subset Definition Level 1.
The following sections, in conjunction with the Device Profile Document, provide a
complete interoperability/configuration guide for the TR-2100:
• The Implementation Table
• The Point List Tables
• Configuration methods
DNP V3.00
DEVICE PROFILE DOCUMENT
Vendor Name: AMETEK Power Instruments
Device Name: TR-2100 Digital Transient Recorder, using the Triangle MicroWorks, Inc. DNP 3.0 Slave
Source Code Library, Ver 2.19
Highest DNP Level Supported:
For Requests: Level 1
For Responses: Level 1
Function:
Master
7 Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
For static (non-change-event) object requests, request qualifier code 06 (no range – or all points) is supported.
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received 292
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
um Data Link Re-tries:
urable from 0 to 255 via Displa
Station32
Maximum Application Layer Re-tries:
None
s Data Link Layer Confirmation:
urable as: Never, Onl
for multi-frame messages, or Always via DS32
s Application Layer Confirmation:
endin
multi-fragment responses
mes