Bundguard 5 12.01.2022 Rev.4
2.2 Alarms
The BundGuard Issue 5 has numerous alarms that can be triggered by specific events the table below
give details of all the alarms.
Mains Failed (no LCD
text)
The mains supply input have failed.
The combination of the sensor input states
indicates an unknown bund state
Bund water level exceeded
The sensor’s high water probe is short
circuited to the common probe when pump
start probe out of water.
The sensor’s pump start probe is short
circuited to the common probe when sensors
stop probe out of water
The sensor’s pump stop probe is open circuit
when start probe is in water.
The sensor’s pump start probe is open circuit
when high water probe is in water.
The current drawn by Pump 1 has exceeded its
pre-set limit
The current drawn by Pump 2 has exceeded its
pre-set limit
One or more control panel connectors is not
connected correctly
The drive circuitry for Pump 1 has failed in a
pumping state and has been disabled
The drive circuitry for Pump 2 has failed in a
pumping state and has been disabled
The outlet filter (designated filter 1) pressure
has exceeded a pre-set threshold
The outlet filter (designated filter 1) pressure
has exceeded a pre-set threshold
The mains supply has dropped below a usable
level or has been removed completely.
Pump 1 has exceeded a pre-set threshold 3
times and is now disabled from use.
Pump 1 has exceeded a pre-set threshold 3
times and is now disabled from use.