Bundguard 5 12.01.2022 Rev.4
7
2.2 Alarms
The BundGuard Issue 5 has numerous alarms that can be triggered by specific events the table below
give details of all the alarms.
Alarm (LCD Text)
Indicator
Cause of Alarm
Mains Failed (no LCD
text)
none
The mains supply input have failed.
ER0 Probe Error
System Fault
The combination of the sensor input states
indicates an unknown bund state
High Water
High Water
Bund water level exceeded
High Oil
High Oil
Bund oil level exceeded
ER 1 HIGH SHORT
System Fault
The sensor’s high water probe is short
circuited to the common probe when pump
start probe out of water.
ER 2 START SHORT
System Fault
The sensor’s pump start probe is short
circuited to the common probe when sensors
stop probe out of water
ER 3 STOP OPEN
System Fault
The sensor’s pump stop probe is open circuit
when start probe is in water.
ER 4 START OPEN
System Fault
The sensor’s pump start probe is open circuit
when high water probe is in water.
Pump1 > limit
System Fault
The current drawn by Pump 1 has exceeded its
pre-set limit
Pump2 > limit
System Fault
The current drawn by Pump 2 has exceeded its
pre-set limit
Connector N/C
System Fault
One or more control panel connectors is not
connected correctly
Pump1 disable
Pump 1
Disable
The drive circuitry for Pump 1 has failed in a
pumping state and has been disabled
Pump2 disable
Pump 2
Disable
The drive circuitry for Pump 2 has failed in a
pumping state and has been disabled
Pressure1 > lim
System Fault
The outlet filter (designated filter 1) pressure
has exceeded a pre-set threshold
Pressure2 > lim
System Fault
The outlet filter (designated filter 1) pressure
has exceeded a pre-set threshold
Batt engaged
System Fault
The mains supply has dropped below a usable
level or has been removed completely.
Pump1 >Cur Disab
none
Pump 1 has exceeded a pre-set threshold 3
times and is now disabled from use.
Pump2 >Cur Disab
none
Pump 1 has exceeded a pre-set threshold 3
times and is now disabled from use.