TROUBLESHOOTING
Technical Support is available Monday through Friday, 7:00 a.m. to 5:00 p.m. CST, at (800) 972-3710. Use the guide below to identify and correct
system faults. Contact Technical Support before replacing the unit or any components and for additional troubleshooting.
TABLE 3 – TROUBLESHOOTING GUIDE
Symptom Possible Reason Troubleshooting Procedure
Dehumidifier does not turn on/run. No power to unit. Check the wiring to the dehumidifier.
If using a Model A76, check that the control is turned ON.
Check that the circuit breaker has not tripped.
Dehumidifier blower is running but
with little or no airflow.
Pressure drop across dehumidifier is
higher than 0.6"w.c.
Check dehumidifier air filter, replace if heavily loaded.
Check that nothing is obstructing air flow into, or out of the dehumidifier.
Dehumidifier is not draining properly. Drain line blocked or unit not level. Verify that the unit is level.
Check that the p-trap is installed correctly and primed.
Check the drain line for blockages and for a continuous downward slope.
Dehumidifier is producing hot air. Normal function. Air is reheated across the condenser coil, resulting in a temperature rise
between inlet and outlet.