23
4.0 Installation
4.9 Output wiring procedure (continued)
4.9.6 Put the stripped wire end corresponding to Neutral into the terminations block
terminal marked N and tighten the screw.
4.9.7 Put the stripped wire end corresponding to Line into the terminations block
terminal marked L and tighten the screw.
4.9.8 Check that there are no loose wire strands and that the terminations block
screws are sufficiently tightened.
4.9.9 Reattach the power distribution plate to the Isolation Unit.
4.9.10 Check that the output wiring terminations are not strained and reattach the
wiring inspection cover.
,
21
2))
Output
termination
s
block
Output cable
Power distribution
plate
/ 1 3(
L N PE