10
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any
circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV.
If circuit standard cannot be confirmed, use a contact closure switch.
Use one of the following cable types to connect the UPS to the EPO switch:
CL2: Class 2 cable for general use
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
CLEX: Limited use cable for use in dwellings and for use in raceways.
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
T
ERMINAL MODE TO CONFIGURE UPS PARAMETERS
3000 VA models:
Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS.
Connect the serial cable to the serial com connector on the back of the UPS.
1. EXIT the PowerChute Business Edition using the following steps:
From the Desktop, go to Start => Settings => Control Panel => Administrative Tools =>
Services.
Select APC PCBE Server and APC PCBE Agent – right click the mouse and select Stop.
2. Open a terminal program. Example: HyperTerminal
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
3. Double-click on the HyperTerminal icon.
Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.
Select the COM port that is connected to your UPS. The port settings are:
9 bits per second - 2400
9 data - bits 8
9 parity - none
9 stop bit - 1
9 flow control - none
Press ENTER
4. Example for setting the number of external battery packs (SURT192XLBP):
Once the blank terminal window is open, follow these steps to enter the number of battery packs:
Press ENTER to initiate terminal mode. Follow the prompts:
Press 1 to modify UPS Settings. Press e (or E) to modify the number of battery
packs. Enter the number of battery packs, including the internal battery pack
(Number of packs: 1= internal battery module, 2 = 1 SURT192XLBP,
3 = 2 SURT192XLBP, etc.).
Press ENTER.
Follow the prompts.
5. Exit the terminal program.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC RT and is the answer not in the manual?

APC RT Specifications

General IconGeneral
Nominal Output Voltage230V
TopologyDouble Conversion Online
Input Voltage Range160 - 286 V
Nominal Input Voltage230V
Transfer Time0 ms
Emergency Power Off (EPO)Yes
Output Frequency50/60 Hz +/- 3 Hz
Wave TypeSine wave
Battery TypeSealed Lead-Acid (SLA)
Interface PortsUSB
Audible AlarmAlarm when on battery
TypeUPS
Form FactorRack/Tower convertible
Dimensions432 x 482 x 89 mm (17 x 19 x 3.5 in)