EasyManuals Logo

APC RT User Manual

APC RT
21 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
11
5000/6000 VA models:
Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS.
Connect the serial cable to the serial port on the back of the UPS.
1. Open a terminal program. Example: HyperTerminal
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
2. Double-click on the HyperTerminal icon.
Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.
Select the COM port that is connected to your UPS. The port settings are:
9 bits per second - 2400
9 data - bits 8
9 parity - none
9 stop bit - 1
9 flow control - none
Press ENTER
3. Example for setting the number of external battery packs (SURT192XLBP):
Once the blank terminal window is open, follow these steps to enter the number of battery packs:
Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User
Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears
on the screen prior to typing the next character.
Network Management Card defaults:
User Name: apc
Password: apc
Press 1 and ENTER to select Device Manager.
Select the model by entering the corresponding number, then press ENTER.
Press 3 and ENTER to select Configuration.
Press 1 and ENTER to select Battery.
Press 2 and ENTER to change the Battery Settings.
Type in the number of external battery packs (four battery modules per pack), then
press ENTER. (Number of packs: 1= internal battery module,
2 = 1 SURT192XLBP, 3 = 2 SURT192XLBP, etc.)
Press 3 and ENTER to accept the changes.
Press ESC multiple times (5) to return to the main menu.
Press 4 and ENTER to log out.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC RT and is the answer not in the manual?

APC RT Specifications

General IconGeneral
Nominal Output Voltage230V
TopologyDouble Conversion Online
Input Voltage Range160 - 286 V
Nominal Input Voltage230V
Transfer Time0 ms
Emergency Power Off (EPO)Yes
Output Frequency50/60 Hz +/- 3 Hz
Wave TypeSine wave
Battery TypeSealed Lead-Acid (SLA)
Interface PortsUSB
Audible AlarmAlarm when on battery
TypeUPS
Form FactorRack/Tower convertible
Dimensions432 x 482 x 89 mm (17 x 19 x 3.5 in)