1
Introduction
The APC Smart-UPS® RT is a high-performance, uninterruptible power supply (UPS) that provides
protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The
UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances
by internally disconnecting from utility line power. The UPS provides continuous power from the
internal battery until utility power returns to safe levels or the battery is fully discharged.
INSTALLATION
Read the Safety Guide before installing the UPS.
Unpacking
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
UPS (with battery modules disconnected)
Front bezel
Literature kit containing:
Product documentation, Safety Guide,
and Warranty Information
Smart-UPS RT User Manuals CD
Software CD
Serial cable
3000 VA XLI models: three output power cords,
two input power cords
5000/6000 VA XLI models: six output power
cords, Network Management Card
documentation
Specifications
TEMPERATURE
O
PERATING
S
TORAGE
32° to 104° F (0° to 40° C)
5° to 113° F (-15° to 45° C) charge the UPS
battery every six months
MAXIMUM
ELEVATION
OPERATING
STORAGE
10,000 ft (3,000 m)
50,000 ft (15,240 m)
This unit is designed for indoor use
only. Select a location sturdy enough to
handle the weight.
Do not operate the UPS where there is
excessive dust or the temperature and
humidity are outside the specified limits.
Ensure that the air vents on the front
and rear of the UPS are not blocked.
HUMIDITY
0 to 95% relative humidity
WEIGHT
UPS
UPS
WITH
PACKAGING
120 lbs (55 kg)
140 lbs (64 kg)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC RT and is the answer not in the manual?

APC RT Specifications

General IconGeneral
Nominal Output Voltage230V
TopologyDouble Conversion Online
Input Voltage Range160 - 286 V
Nominal Input Voltage230V
Transfer Time0 ms
Emergency Power Off (EPO)Yes
Output Frequency50/60 Hz +/- 3 Hz
Wave TypeSine wave
Battery TypeSealed Lead-Acid (SLA)
Interface PortsUSB
Audible AlarmAlarm when on battery
TypeUPS
Form FactorRack/Tower convertible
Dimensions432 x 482 x 89 mm (17 x 19 x 3.5 in)