EasyManua.ls Logo

APC Smart-UPS RC - Configuration Parameters; Output Voltage; Output Frequency; Number of Battery Strings

APC Smart-UPS RC
21 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/2000/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 16
Output voltage Allows user to select output voltage while on-line.
220 V models 220 Vac 200, 208, 220,
230, 240 Vac
230 V models 230 Vac 200, 208, 220,
230, 240 Vac
Output frequency Automatic
50 ± 3 Hz
60 ± 3 Hz
Automatic
50 ± 3 Hz, 50 ± 0.1 Hz,
60 ± 3 Hz, 60 ± 0.1 Hz
Sets allowable UPS output frequency. Whenever
possible, output frequency tracks input frequency.
Number of
battery strings
1 Number of connected
battery strings
Defines number of connected battery strings for
proper run time prediction.
1000/2000 VA models default setting of 1=432 VAh, 96 V x 4.5 Ah
Refer to XLBP user manual for details on
configuring UPS and # of battery strings.
3000 VA models default setting of 1=691 VAh, 96 V x 7.2 Ah
Refer to XLBP user manual for details on
configuring UPS and # of battery strings.
Function Factory Default User Selectable
Choices
Description

Related product manuals