CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
D. UPS Output:
1. AC Output Nominal Output: 200VAC, 208VAC, 220VAC, 230VAC or
240VAC, user-selectable, Single Phase, 3 wire (Phase + N + G);
2. Output connectors: 8 IEC 320 C13 and 2 IEC 320 C19;
3. Output frequency: 50/60 +/- 3Hz tracking or 50/60 +/- 0.1Hz tracking (user
selectable);
4. AC output voltage distortion: Max. 2% @ 100% linear load; Max. 5% @ 100%
non-linear Load;
5. AC output static voltage regulation: +/-1%;
6. AC output dynamic voltage regulation: +/- 8% maximum for 100% load step at
less than 10ms recovery time;
7. Overload Rating:
a. Online: 105% - infinite; 125% - 1 minute; 150% - 30 seconds;
b. In bypass: Overload is limited by the UPS input circuit breaker which is
rated 16A for 3000VA model, 32A for 5000VA and 6000VA models;
8. Output Power Factor Rating: 0.2 –1.0 lagging, 0.9 to 1.0 leading.
2.3 ENVIRONMENTAL
1. Storage Ambient Temperature: -20C to 60C (-4F to 140F).
2. Operating Ambient Temperature: 0C to 40C (+32F to 104F). 25C (77F) is
ideal for most battery types).
3. Relative Humidity: 0 to 95% non-condensing
4. Storage altitude: 15,000m (50,000 feet) above sea level
5. Operating altitude: 3000m (10,000 feet) above sea level. At altitude of 3,000m
the UPS must be loaded up to a maximum of 90% of its nominal capacity only.
6. Audible noise: less than 55dBA at 1m (3 feet).
2.4 INPUT PFC POWER STAGE
A. The input PFC power stage of the UPS constantly rectifies the power imported from the
mains input of the system, converting input mains AC power to DC power for precise
regulation of the DC bus voltage, battery charging, and output power stage (inverter)
regulated output power.