EasyManuals Logo

APC Symmetra PX Guide Specifications

APC Symmetra PX
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Page 1 1/25/2013
APC by Schneider Electric
APC Symmetra PX
Uninterruptible Power Supply
Guide Specifications
96/160 kW
Uninterruptible Power System
THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE
(CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE ARCHITECT OR THE
ENGINEER TO MEET THE REQUIREMENTS OF THE PROJECT. COORDINATE THIS SECTION WITH OTHER
SPECIFICATION SECTIONS IN THE PROJECT MANUAL AND WITH THE DRAWINGS.
WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO “PROVIDE, “INSTALL”, “SUBMIT”, ETC., IT SHALL MEAN
THAT THE CONTRACTOR, SUBCONTRACTOR, OR CONTRACTOR OF LOWER TIER SHALL “PROVIDE”, “INSTALL”,
SUBMIT”, ETC., UNLESS OTHERWISE INDICATED.
THIS SECTION IS WRITTEN TO INCLUDE THE 2004 MASTERFORMAT AND THE 1995 MASTERFORMAT VERSIONS.
WHERE APPLICABLE, THESE ITEMS ARE BRACKETED AND, IN EACH CASE, UNLESS OTHERWISE INDICATED, THE
FIRST CHOICE APPLIES TO THE 2004 MASTERFORMAT AND THE SECOND CHOICE APPLIES TO THE 1995
MASTERFORMAT.
SECTION [26 33 63] [16611]
SOLID STATE UNINTERRUPTIBLE POWER SUPPLY
PART 1 - GENERAL
1.1 SUMMARY
A. This specification describes the operation and functionality of a continuous duty, three-phase,
solid-state, static Uninterruptible Power System (UPS) hereafter referred to as the UPS. The
UPS shall utilize a rack-mounted redundant, scalable array architecture. The system power
train shall be comprised of hot swappable / user replaceable 16 kVA/16 kW power modules,
which shall operate in parallel. Each 16 kVA/16 kW power module contains a full rated input
rectifier / boost converter (hereafter referred to as Input Converter), full rated output inverter,
and battery charging circuit. The system shall also comprise of a user-replaceable continuous
duty hot swappable bypass static switch module, hot swappable / user replaceable battery
modules, redundant control modules, redundant logic power supplies, and LCD interface
display. All of the above system components are housed in a standard, 600 mm wide, 1070
mm deep, 2000 mm high equipment rack.
B. In addition, this specification describes the performance, functionality, and design of the
Maintenance Bypass, Power Distribution and extended Runtime cabinet, hereafter referred to
as the PDU-XR, the Battery System, and connectivity solutions.
C. The UPS and associated equipment shall operate in conjunction with a primary power supply
and an output distribution system to provide quality uninterrupted power for mission critical,
electronic equipment load.
D. All programming and miscellaneous components for a fully operational system as described
in this specification shall be available as part of the UPS.
1.2 SUBMITTALS
A. Proposal Submittals:
1. As bid system bill of materials.
2. Product catalog sheets or equipment brochures.
3. Product guide specifications.
4. System single-line operation diagram.
5. Installation information, including weights and dimensions.
6. Information about terminal locations for power and control connections.
7. Drawings for requested optional accessories.

Other manuals for APC Symmetra PX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC Symmetra PX and is the answer not in the manual?

APC Symmetra PX Specifications

General IconGeneral
Noise level61 dB
Output power32000 W
Output power capacity32 kVA
Emergency Power Off (EPO)Yes
Battery typeVRLA
Dimensions (WxDxH)1200 x 1070 x 1991 mm
Battery technologySealed Lead Acid (VRLA)
Battery recharge time3.5 h
CertificationEN 50091-1, EN/IEC 62040-3, EN/IEC 62040-1-1, FCC Part 15 Class A, VFI-SS-111
Product colorBlack
Operating altitude0 - 999.9 m
Non-operating altitude0 - 15000 m
Storage temperature (T-T)-15 - 40 °C
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %
Weight and Dimensions IconWeight and Dimensions
Weight1095400 g
Package weight1189000 g