EasyManua.ls Logo

Apex Digital PC - Configuring Serial Communications; Unit ID; Modbus RTU Configuration; Modbus Address

Default Icon
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 Setup
Configuring Serial Communications
MENU SETUP RS-232 Serial or RS-485 Serial
You can operate the pressure controller remotely via its data connection for easy streaming
and logging of all data. Before connecting the pressure controller to a computer, ensure
that it is ready to communicate with your computer by checking the options in this menu.
For more on how to issue commands from a computer, see page 20.
Unit ID
SETUP RS-232 Serial or RS-485 Serial Unit ID
The unit ID is the identifier that a computer uses to distinguish your device from other, similar
devices when connected to a network. Using the unit ID letters AZ, you can connect up
to 26 devices to a computer at the same time via a single  port. This is called polling
mode (page 20). Unit ID changes take eect when you select
SET.
If you select “
@” as the Unit ID, the pressure controller will enter streaming mode when
you exit the menu (page 21).
Modbus RTU Configuration
SETUP RS-232 Serial or RS-485 Serial Modbus Address
SETUP RS-232 Serial or RS-485 Serial Modbus
Modbus Address
The Modbus address is the identifier that a computer or programmable logic computer (PLC)
uses to distinguish your device from other devices when connected to a Modbus network.
Values of 1–247 are available for use.
Managing Setpoint with an Idle Modbus Connection
If a Modbus connection is idle for a specified amount of time, the device can be configured
to set a zero setpoint, or maintain the previous setpoint. The idle time will be infinite by
default and can be set in seconds up to 99999.9 seconds (1 day, 3 hours, 46 minutes, 39.9
seconds).
Baud Rate
SETUP RS-232 Serial or RS-485 Serial Baud Rate
Baud rate is the speed at which digital devices transfer information. The pressure controller
has a default baud rate of 19200 baud (bits per second). If your computer or software uses
a dierent baud rate, you must change the pressure controllers baud rate in the BAUD menu
to ensure they match. Alternatively, you can change your computers baud rate in Windows®
Device Manager. Baud rate changes take eect once you press SET, but you may need to
restart the software for it to recognize the change.
The serial communication menu.
Choosing a unit ID, or streaming.
Baud rate options.
The Modbus address menu.
The Modbus idle menu.
Setting a Modbus idle disconnect
time.

Table of Contents