112 Options List
C.11 Option 27: 8-Channel High Drive
C.11.1 General Description
Option 27 provides eight independent, IRIG-B buffered outputs, each capable of driving multiple
loads. Outputs are short circuit and surge protected. Each output is individually configurable for
either modulated or unmodulated IRIG-B signals via jumper settings as illustrated in Figure C.8.
C.11.2 Specifications
Output Selection
Each output is jumper selectable for either a Modulated or Unmodulated signal. See Figure C.8
for jumper locations and configuration settings.
Number of Channels: Eight (8).
Signal Levels:
Modulated: 4.5 Vpp with 20-Ohm source impedance; each channel
will drive a 50-Ohm load to 3 Vpp minimum; requires
Option 92 in Model 1093A/B/C.
Unmodulated: +5-V open-circuit; +4 V minimum at 250-mA
load current each channel will drive 25 Schweitzer
SEL-3xx (in parallel) or 50 SEL-2xx (in series/parallel)
relays at 10 mA per relay.
Maximum Load (per driver):
Modulated: No Limit: will drive a short circuit.
Unmodulated: 250-mA peak current; pulse-by-pulse shutdown if load
current exceeds internal limit (self-resetting).
Output Connector
16-position pluggable 5-mm (Phoenix-type) terminal strip with eight 2-position mating connec-
tors.
C.11.3 Option Setup
Using Front Panel Keys
To set up Option 27 from the front-panel keys, please follow the guidelines in Section 7.13.
Using RS-232C Port