Argo AGHP081PH - Current Limit Setting; Address Configuration; Refrigerant Recovery; Water Tank Heater Control Logic

Argo AGHP081PH
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Instructions
22
2.4.14 Current Limit
[Operation Instructions]
1. At the commissioning parameter setting page, by touching “Current limit”, it can be set to “On” or “Off”.
2. When it is set to “On”, it is able to set the limited current value.
3. After that, this setting will be saved by touching the “Save” icon.
[Notes]
This setting will be memorized upon power failure.
2.4.15 Address
[Operation Instructions]
At the commissioning parameter setting page, by touching “Current limit”, it can be set the address.
[Notes]
It is used to set the address of the control panel for being integrated to the centralized control system.
This setting will be memorized upon power failure.
The setting range is 1~125 and 127~253.
The defaulted address is 1 upon first power-on.
2.4.16 Refrigerant Recovery
[Operation Instructions]
At the commissioning parameter setting page, by touching “Refri. recovery”, it will access to the refrigerant
recovery page.
When “Refri. recovery” is set to “On”, the control panel will go back to the home page. At this time, any touch
operation except ON/OFF will get no response, with a prompt dialog box popping up, saying “The refrigerant recovery
is running!” By touching ON/OFF, refrigerant recovery will quit.
[Notes]
This function is allowed only when the unit has just repowered and not turned on. For the unit which once has
been put into operation, this function is unavailable, alerting “Wrong operation”.
This function will not be memorized upon power failure.
2.4.17 Control Logic of the Water Tank Heater
[Operation Instructions]
At the commissioning parameter setting page, by touching “Tank heater”, it will access to the setting page of control
logic for the water tank heater.
[Notes]
“Reserved” will be displayed when the water tank is unavailable.