EasyManua.ls Logo

Armstrong 6100 - Page 12

Armstrong 6100
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
High Limit Humidistat
Remove the jumper tab from ground and in of high limit/pressure switch connections and wire the high
limitstatbetweentheseterminals.RefertoFigure10-1(theoverallwiringdiagram)formoreinform
ation. A duct mounted high limit humidistat is recommended to prevent over-saturation of the duct air.
Useanon-offcontrollerthatopensonfault(highhumidity).Humidistatshouldbesetforamaximum
of90%RH.Locatethehighlimithumidistatapproximately3m(10feet)downstreamofthedispersion
manifold.If3m(10feet)isnotavailable,consultthefactory.Note: High limit humidistat will be wired in
series with duct pressure switch, if used, see Figure 10-1.
Airflow/Pressure Switch
An airflow switch is recommended to deactivate the humidifier when there is insufficient air flow in a
duct system. A duct pressure switch is preferred as an airflow sensor. The pressure switch should
openoninsufficientairflow(opensonfault).Airflowswitchshouldbemountedinsupplyairduct
upstream of humidifier dispersion. Remove the jumper tab from ground and in of high limit/pressure
switchconnectionsandwiretheairflowsensorbetweentheseterminals.SeeFigure10-1(theoverall
wiringdiagram)formoreinformation.Completeinstallationandwiringinstructionsarecontainedinthe
duct pressure switch package.
State light will flash green if either high limit or air pressure switches are open.
Modulating High Limit Humidistat/Sensor
AmodulatinghighlimithumidistatmaybeusedonapplicationssuchasVariableAirVolume(VAV)
or in situations where the duct RH required to maintain the room set point is near saturation. The
modulating high limit alleviates the humidifier from operating in on/off if working near the high limit set
point. See Figure 10-1 or Figure 11-2 for wiring.
Alarm Circuit
Theterminals3&4(normallyopenrelayexternalalarm)areconnectionsforaclassIINECalarm
circuit(switchclosureonly,1amp.maximum@24Vdcor0.5amp.@125Vac).Theswitchwillclose
if the unit encounters an error or when service life has expired it will not engage if high humidity/sail
switch circuit is open.

Related product manuals