Step 13
Valve Calibration
Must be used after replacing the following parts:
• Proportioning Assembly
• PCB
• Drive Housing
• Gear Drive Assembly
1
2
3
4
Turn power on to the reassembled DRV80 and connect to a Laptop / PC device.
Run the The Brain® DRV Programming Software and go to the Options screen.
Click Off under Valve Control.
Click Calibration Set.
continued...