EasyManua.ls Logo

Aros Syncro 800 - Technical Specifications

Default Icon
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 36 -
TECHNICAL SPECIFICATIONS
MODEL Syncro 800 Syncro 1000 Syncro 1500 Syncro 2000
Capacity 230Vac -25% / +20%
Frequency 50 o 60Hz +/-5% (auto sensing)
INPUT
Maximum Current 5 A 6.3 A 9.4 A 10 A
Voltage
(on battery)
Simulated sinus wave 230Vac +/- 5%
Frequency
(on battery)
50 or 60Hz +/-0.5% (auto sensing)
Voltage Regulator
AVR
AVR automatically increases the output voltage by 17% if the input voltage drops by -
10%-26% below nominal. AVR decreases the output voltage by 15% if the input
voltage increases by +9% -+20% above nominal
Transfer time Typically 6-8 ms
Nominal power VA 800 1000 1500 2000
Nominal power W 480 600 900 1200
OUTPUT
Current 3.48A 4.35A 6.52A 8.70A
EMI/RFI Filter 10dB at15MHz, 50dB at 30MHz
PROTECTION AND
FILTERS
Protection against
overloads and short
circuits
Mains: thermal protection switch for overloads and short circuits
Battery: the UPS shuts down after 30 seconds if the load is between 100 ~ 110% of
the nominal, after 5 seconds if it exceeds 110%, or immediately in the event of a
short circuit.
Type Lead acid, sealed, maintenance free
Model 2x12V 7Ah 2x12V 7Ah 2x12V 9Ah 3x12V 9Ah
Typical recharge time 6-8 hours
BATTERY
Protection Protection against battery failure, battery replacement indicator
Net weight (Kg) 13,5 13,5 14,7 20,3
Dimensions(mm)
WxDxH
140x370x180 140x400x217
Input plug IEC 320-10A
PHYSICAL
CHARACTERISTICS
Output plug N°4 x IEC 320-10A
Battery Mode Slow beep (approx. 0.20Hz)
Battery Failure Fast beep (approx. 1Hz)
Overload <110% Fast beep (approx. 1Hz)
Overload >110% Continuous beep
ALARMS
Disable buzzer YES
RS-232 Interface Bi-directional communication port
INTERFACE
RS-232 protocol PSGPSER-0103
Safety EN 50091-1-1 and EEC specifications 73/23 and 93/68
COMPLIANCE
EMC EN 50091-2 cl.B and EEC specifications 89/336, 92/31 and 93/68
ENVIRONMENTAL
CONDITIONS (1)
Environmental
Conditions
max. altitude: 6,000 metres, 0-90% non condensing humidity
0-40°C
OTHERS Noise Level <50dBA (1m from source )
(1) In order to prolong battery life, make sure that the UPS is used/stored at a temperature of 20-25°C and
keep it connected to the mains to preserve the battery charge.