EasyManuals Logo

Asco 300 Series User Manual

Asco 300 Series
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
INSTALLATION (continued)
1 --- 4
observe these lights
Figure 1–5. Standard controls and indicators.
2–VoltageChecks
First check nameplate on transfer switch; rated voltage
mustbethesameasnormalandemergencylinevoltages.
Verify that the feeders have been
connected to the proper lugs.
Use extreme caution when using a meter
to measure voltages in the following
steps. Do not touch power terminals;
sh oc k , burns , or death could result !
Perform steps 1 through 6 at the right. Observe the status
lights. See Figure 1–5.
Black circle means light is on.
White circle means light is off.
* If necessary, adjust voltage regulator on the generator
according to the manufacturer’s recommendations. The
Automatic Transfer Switch will respond only to the rated
voltage specified on the Transfer Switch nameplate.
Also see page 4–1 for the HI–LOW voltage adjust setting in
the controller. The LOW setting shifts all voltage settings
down 4. 2%; for example, 240 V to 230 V.
1
Close the normal source circuit
breaker. The Normal T ransfer
Switch Position and the Normal
Source Accepted lights should
come on.
Source Accepted
Normal
Emergency
2
Use an accurate voltmeter to
check phase to phase and
phase to neutral voltages pres-
entatthetransferswitchnormal
source terminals.
3
Close the emergency source
circuit breaker. (Start generator,
if necessary.) The Emergency
Source Accepted light should
come on.
Source Accepted
Normal
Emergency
4
Use an accurate voltmeter to
check phase to phase and
phase to neutral voltages pres-
ent a t the transfer switch emer-
gency source terminals.*
5
Useaphaserotationmeterto
check phase rotation of emer-
gency source; it must be the
same
as the normal source.
A
B
C
6
Shut down the engine–genera-
tor, if applicable. The Emergen-
cy Source Accepted light should
go off. Then put the starting
control selector sw itch (on the
generator set) in the automatic
position. Close enclosure door.
Source Accepted
Normal
Emergency
Now continue to 3 Electrical Operation on next page.

Other manuals for Asco 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Asco 300 Series and is the answer not in the manual?

Asco 300 Series Specifications

General IconGeneral
TypeAutomatic Transfer Switch
Poles2, 3, 4
Enclosure TypeNEMA 1, 3R, 4, 4X, 12
Amperage Range30-4000 Amps
CertificationsUL 1008, CSA
OperationAutomatic
Transfer TypeOpen, Closed, Delayed
Control PanelMicroprocessor-based
StandardsIEEE

Related product manuals