AC25/30QTP-1 and -3 Operations Manual.... 48
7.3 LOAD MANAGEMENT OPERATION, cont.
7.3.5 Quick Setup of Shore Cord Alarm, Single, Master, or Slave Converters
1. Turn on the red Disconnect switch of both converters and wait 15-20 seconds for initialization.
2. Press the SHORE POWER + F2 buttons on both converters.
3. Press the Cursor (F4) button to advance to the ALARM AT % setting.
4. Set the converter ALARM AT % using the More/Less (F1/F2) buttons.
5. Press the Cursor (F4) button to advance to the ALARM enable setting.
6. Set the converter ALARM enable using the Enable/Disable (F1/F2) buttons.
7. Press the Exit (F5) button to save the settings and exit.
8. Turn on the converters and place online as usual. Alarm will occur when loading reaches the
ALARM AT % setting.