66
Identifier Yes No
Do the four green LEDs light up?

Does the audible alarm signal switch off?

Does the emergency key light up?

Tamper alarm on the escape door module
Activate locking system.
Open the protective cover on the escape door module.
Identifier Yes No
Do the red LEDs light up?

Do the yellow LEDs flash?

Is the tamper alarm (audible alarm signal) triggered?

Does the door remain locked? (test manually)

Close the protective cover on the escape door module.
Identifier Yes No
Do the red LEDs light up?

Do the yellow LEDs flash?

Does the audible alarm signal remain active?

Does the door remain locked? (test manually)

Re-set alarm.
Tamper alarm on the key switch module
Activate locking system.
Remove the cover from the key switch module.
Identifier Yes No
Do the red LEDs light up?

Do the yellow LEDs flash?

Does the audible alarm signal remain active?

Does the door remain locked? (test manually)


Table of Contents