57
The available profiles are optimised default settings, which you can
access.
The parameters are adjusted at the factory.
These factory settings and the possible adjustment range are shown in
the following table. All values in seconds.
Parameters Factory
Adjustable
setting
from to
Temporary release 5 1 255
Hold-open function 50 1 3600
monitoring unit 60 1 3600
Pre-alarm 10 1 3600
Alarm signal 180 0 255
Guidance signal 600 0 9999
Activation delay 0 0 255
Configuration using
FT Manager
(1385 - networked)
If changes are made, you must always select Profile ‚0‘ (called functions
templates in
FT Manager
) as it is the only place where changes can be
saved.
Additional information
Profile ‘0’ is set by default when the device is delivered.
Profile Description
Input
Output
0 External temporary
release
Combined with a motorized or sole-
noid lock, or with an electric strike,
to release the door in the direction of
escape
1 External temporary
release
To connect to an external locked mode
monitoring unit
2 External temporary
release
To actuate a door drive
Profile settings