EasyManua.ls Logo

Atlas Copco GA 110 VSD+ - Page 65

Atlas Copco GA 110 VSD+
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reference Description
(7) Service mode
To preserve the protection degree of the electric cubicle and to protect its components
from dust from the environment, it is mandatory to use a proper cable gland when
connecting the supply cable to the compressor.
Warnings
Obey local regulations if they are stricter than the regulations mentioned in this
document.
Obey the applicable electrical directives when installing and connecting the
compressor to the power circuit:
IEC 60204-1
IEC 60364-5-52
CSA/UL
UL: UL508A
CSA: C22.2
The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage. It is however highly recommended to keep the voltage drop over
the supply cables at nominal current below 5% of the nominal voltage (IEC
60204-1).
Use the original cable entry.
Full load (compressor) package currents are calculated and available on Technical
data sheet. For cable section selection purposes, we suggest to add 10% to
compensate for any under-voltages that might occur in the installation.
Use copper wires only.
Caution
Always double-check the fuse size versus the calculated cable size. If
required, reduce the fuse size or enlarge the cable size.
Cable length should not exceed the maximum length according to IEC 60204
(table.10).
Display the fuse type information next to the fuse holder of the mains branch.
Connect the power cable with the correct cable lugs on the terminals in the
electrical cabinet.
Do not connect more than one (1) cable lug at one side of a contactor terminal or
copper bar, unless specified otherwise.
Respect a minimum of 10 mm IEC (1/2” CSA/UL branch circuit) between stripped
cable ends for low voltage installations.
Fuses are maximum allowed values to protect installed compressor electrical
panel.
Apply the listed cable sections on main supply cables AND earth cable.
Do not exceed the ambient temperature listed in the Limits section to avoid cable
damage.
Mount all cables on a horizontally ventilated cable tray.
Do not stack or group cables as this avoids heat dissipation.
Connect the power cable with the correct (CSA certified) cable lugs on the
terminals in the electrical cabinet.
Respect a minimum distance of 10 mm (0.4") between stripped cable ends.
Use only the prescribed cable types:
IEC: XLPE 90 °C (194 °F)
CSA-UL: (R, RW, T) multicore 110 °C (230 °F)
Display the fuse type information next to the fuse holder of the mains branch.
Instruction book
9829 3178 63 63

Table of Contents

Related product manuals